The installation site of the photovoltaic (PV) station is located at “Agios Georgios”, D.K Schimatariou , D.E Schimatariou , Municipality of Tanagra in Viotia Grrece. The area of the plot, as seen in the aerial photo, is 15,764 sq m .
BASIC EQUIPMENT
PV FRAMES
POWER INVERTERS
PV FRAMES SUPPORT SYSTEM
INFRASTRUCTURE PROJECTS
CONFIGURATION OF THE SPACE
SUBSTATION
KVA substation was installed at the entry point of the plot to gather the power from the inverters with the least losses.
The equipment has been designed, manufactured and tested according to the following international standards: IEC standards
62271-200 | High-voltage switchgear and control gear – Part 200: AC metal enclosed switchgear and control gear for rated voltage above 1 kV and up to and including 52 kV. |
60470 | Medium Voltage Relays . |
62271-103 | High voltage switches – Part 1: switches for rated voltages above 1 kV and less or equal to 52 kV. |
62271-105 | High-voltage switchgear and control gear – Part 105: High voltage Alternating current switch-fuse combinations. |
60801 | Electromagnetic Compatibility for measurement instruments |
62271-100 | High-voltage switchgear and control gear – Part 100: High-voltage alternating current circuit breakers. |
62271-102 | High-voltage switchgear and control gear – Part 102: High-voltage Alternating current disconnectors and earthing switches. |
60044-1 | Instrument transformers – Part 1: Current transformers. |
60044-2 | Instrument transformers – Part 2: Voltage transformers |
60044-8 | Instrument transformers – Part 8: Low Power Current transducers |
60529 | Ingress protection rating . |
60694 60255 |
General Specifications for Medium Voltage Panels Protection Relays |
Quality Certificates
The quality system for the design and manufacture of the SM6 series cells is harmonized with the requirements and standards of the ISO 9001 quality regulations.
OTHER ELECTRICAL EQUIPMENT
DC CABLES
CABLES A .C
COMMUNICATION CABLES
GROUNDING AND LIGHTNING PROTECTION
Earthings, external protection and equivalent protections of the park.
Earthing (external protection and equipotential connections) complies with IEC (EN) 62305 – 3 for Protection Level III.
PROTECTION OF ELECTRICAL AND ELECTRONIC DEVICES FROM SHOCK VOLTAGE
- Protection of the General Installation Panel H.T. from direct and indirect AC lightning strikes.
- self-consumption table from direct and indirect lightning strikes in alternating current.
- Protection of sub-tables self-consumptions from indirect lightning strikes in alternating current.
- CCTV circuit protection indirect lightning strikes on direct current.
PV STATION MONITORING SYSTEM
The facilities include appropriately selected sensors for measuring parameters and data of the operation of the PV plant, i.e. solar radiation intensity sensors, outdoor temperature and operating temperature sensors of the PV generators, instantaneous power and energy meters at the output of the PV and inverter etc. The continuous recording system of the system operating parameters is compatible with the inverter technology . The monitoring system records and stores the data to allow continuous analysis of the performance of the PV park.
SECURITY SYSTEM
- Perimeter Fence Breach Detection System
- CCTV Closed Circuit Television Monitoring System
- Lighting
NETWORK CONNECTION
The connection of the project in question to the network was carried out with underground cables of suitable cross-section to minimize losses at the point indicated by DEDDIE.